Vertically and horizontally scalable
The DPA 500 provides power protection from 100 to 500 kW (one to five modules) in a single cabinet (vertical scalability). The cabinets can operate in a parallel configuration to form a system of up to 3 MW (horizontal scalability).
True parallel architecture
The advanced UPS design of the DPA 500 provides the highest degree of protection in critical applications where the load needs to be supplied with quality power. This UPS system uses decentralized parallel architecture, providing the highest level of reliability and availability with true redundancy between modules.
| GENERAL DATA |
DPA 500 |
| System power range |
100 kW–3.6 MW |
| Nominal power/module |
100 kW |
| Nominal power/cabinet (capacity) |
500 kW |
| Output power factor |
1.0 |
| Topology |
Double conversion, transformerless, modular, Distributed Parallel Architecture |
| Parallel configuration |
Up to 5 modules in one frame (500 kW), up to 6 frames in parallel (3 MW) |
| Cable entry |
Bottom or top (non-standard) |
| Serviceability |
Fully front serviceable |
| Rear side protection |
B1-a (standard) |
| INPUT |
|
| Nominal input voltage |
3-phase 400/230 V + N, 3-phase 480/277 V + N, 3-phase 208/120 V + N |
| Voltage tolerance |
±10% (100% load), ±15% (80% load), ±20% (50% load), ±30% (30% load), ±35% (15% load) |
| Input harmonic distortion THDi |
<3% (at 100% load) |
| Frequency range |
35–70 Hz |
| Power factor |
0.99 @ 100% load |
| Walk-in/start feature |
Yes |
| OUTPUT |
|
| Nominal output voltage |
3-phase 400/230 V + N, 3-phase 480/277 V + N, 3-phase 208/120 V + N |
| Voltage tolerance |
±1% (at static load), ±5% (at overload) |
| Voltage distortion THDv |
<2% at linear load / <3% at non-linear load |
| Frequency |
50 or 60 Hz (selectable) |
| WEIGHT & DIMENSIONS |
|
| Weight (6-module system) |
1275 kg (500 kW system, without batteries) |
| Dimensions (W×D×H) |
1650 × 915 × 1955 mm |
Highlights
- 100 kW Incremental Power Module
- Unlimited Space Power in Flexible Structure
- Extended Input Range: 100 kW to 3 MW
- Input Power Factor 1.0, No Loss
- Service Time = % AC Output W
- Maintainable on a Single Module
- High Loading Density
- Extended Static Module Replacement (SMR)
- Extended Fast Backup
- Dedicated Battery Input (Standard)
- Static Input Cutoff Control (Standard)
- Monitoring and Control Interface
- Inputs for External Modules
- Static Bypass Switch (Single-Bypass)